call now 01785 254 597

ATC-N118

ATC-N118 Temperature Controller

ATC-N118

The ATC-N118 meter is designed for temperature measurements. The device is equipped with one resistance-type Pt100/500/1000 input or thermocouple input which can operate with K, S, J, T, N, R, B, and E type thermocouples. The inputs feature with fully linearized characteristics.

Thanks to the tight housing with high (IP 67) protection degree, this device is particularly suitable for operations in harsh environments. The 24V DC / 100 mA output is designed to supply measuring transducers, and the RS-485 port enables data transmission in production process monitoring systems. The REL / OC control outputs can adjust the level of measured signal and are controlled according to one or two threshold values.

Moreover, the meter can be equipped with analogue outputs, according to the customer selection: active current output, passive isolated current output or active voltage output. The meter may be configured with no need to open the case, by using the remote controller or with free S-Config software via the RS-485 communication port.


Key Features

  • Temperature meter in wall-mounted IP 67 case
  • Input: thermoresistance or thermocouple
  • 0 or 2 REL / OC outputs
  • Analogue output: active or passive, power supply output: 24V DC
  • RS-485 / Modbus RTU
  • Automatic recognition of 3 and 4-conductor connection (RTD inputs)
  • Automatic compensation of TC cold ends temperature
  • Signal peak value detection
  • Free configuration software S-Config

ATC-N118 Temperature Controller Specifications

  • Specifications

    Specifications

    Number of inputs: 1

    Input type: RTD, TC, voltage (mV) 

    Input range: Pt100, Pt500, Pt1000: -100...+600°C, TC K: -200...+1370°C, S: -50...+1768°C, J: -210...+1200°C, T: -200...+400°C, N: -200...+1300°C, R: -50...+1768°C, B: +250...+1820°C, E: -200...+1000°C -10...90mV

    Output type: Depends on configuration: relay I=1A, U=30V DC/250V AC (cosø=1), Open Collector: I=30 mA, U=30V DC, P=100 mW 0/4...20 mA: active current, operating range 0...24 mA max., load resistance 700 Ω max., resolution 13 bit 4...20 mA: passive current, isolated, operating range 2,8...24 mA max., load resistance 600 Ω@24VDC, resolution 13 bit 0/1...5V, 0/2...10V: active voltage, operating range 0...11V max., load resistance min. 2000 Ω, resolution 13 bit

    Power supply: 16...35V AC, 19...50V DC 85..260V AC/DC

    Display: LED, 4 x 20 mm, red LED, 4 x 20 mm, green

    Communication Interface: RS-485 / Modbus RTU

    Transmission Parameters: 1200...115200 bit/s, 8N1 / 8N2

    Operating Temperature: 0...+50°C, -20…+50°C

    Protection Class: IP 67

    Case Material: ABS, polycarbonate

    Mounting: Panel

    Case Dimensions: 110 x 80 x 67 mm

  • Applications

    Applications

    • Temperature meter in wall-mounted IP 67 case
    • Analogue output: active or passive, power supply output: 24V DC
    • RS-485 / Modbus RTU
    • Automatic recognition of 3 and 4-conductor connection (RTD inputs)
    • Automatic compensation of TC cold ends temperature
    • Signal peak value detection
  • Data Sheets

 

More Information

Search